The APC Manager tool gives a picture of the auxiliary power consumption to the management, that is, the consumption of power by the auxiliary components of main equipment. For example, a boiler. To run, a boiler needs motors, pumps, fans etc that consume power. Suppose the Turbine generates 150 MW power, the auxiliary equipment consumes about 8 to 10 percent of the power generated by the turbine, which is the acceptable usage.
On the APC dashboard at the highest level, the power consumption by a unit is shown and then drills down to the equipment level. This data helps in streamlining the power consumption by identifying the areas of overconsumption.
To view APC details at Unit level:
The page shown appears.
The histogram displays the daily auxiliary power consumption at the unit level. KW/MW consumed.
Figure 117. APC manager page
To view APC details at system level:
The breakdown of the power usage by system is shown.
For example, Fuel Supply System, Condensate cycle System, Bfp System, Cooling Water System, and Pcfb (boiler) System
Figure 118. APC Dashboard
To view APC details at the total equipment level:
The breakdown of power usage at equipment level is shown.
For example, total consumption by all the fans combined. For example, ACW Pump, Cw Pump, Cooling Tower Fan, Cooling Water Fan, Counter Cooling Water Pump.
Figure 119. APC details
To view APC details at individual equipment level:
Figure 120. System overview
To view APC details at sensor level:
For example, if the furnace pressure is good, the equipment uses less power and if the furnace pressure is bad it uses more power.
Figure 121. APC overview at sensor level